0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES
0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES

0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES

• YAXZ3V-R
• NA2XFGBY

Öznur icon
Code YAXZ3V-R, NA2XFGBY
Standarts TS IEC 60502-1, VDE 0271
Construction Aluminum Conductor, XLPE insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Sheath
Application Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
Weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(maks.) resistance
at 
20 °C (maks.)
 
Current carrying capacity 
(approx.)
(mm²) (mm) (kg/km) (cm) (ohm/km) Ground(A) 
at 20°C
Air(A)
at 30°C
4x25 rm 26,5 1300 160 1,200 111 100
4x35 rm 30,0 1550 180 0,868 132 122
4x50 rm 33,0 1950 200 0,641 157 147
4x70 rm 37,5 2500 220 0,443 195 189
4x95 rm 41,5 3100 230 0,320 233 232
4x120 rm 46,5 3800 240 0,253 266 270
4x150 rm 52,0 4600 250 0,206 299 308
4x185 rm 57,0 5450 220* 0,164 340 357
4x240 rm 63,0 6700 230* 0,125 401 435
4x300 rm 70,0 8300 240* 0,100 455 501
4x400 rm 81,0 10650 250** 0,0778 526 592
rm:Stranded conductor, * For 500 m. Cable, ** For 250 m. Cable