0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES
0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES

0,6/1 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, PVC OUTER SHEATH AND FLAT STEEL SHIELD POWER CABLES

• YAXZ3V-R
• NA2XFGBY

Öznur icon
Code YAXZ3V-R, NA2XFGBY
Standarts TS IEC 60502-1, VDE 0271
Construction Aluminum Conductor, XLPE insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, Pvc Outer Sheath
Application Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
Weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(maks.) resistance
at 
20 °C (maks.)
 
Current carrying capacity 
(approx.)
(mm²) (mm) (kg/km) (cm) (ohm/km) Ground(A)
at 20 °C
Air(A)
at 30°C
3x25 rm 24,5 1100 140 1,200 111 100
3x35 rm 27,0 1300 150 0,868 132 122
3x50 rm 30,0 1650 180 0,641 157 147
3x70 rm 35,0 2100 210 0,443 195 189
3x95 rm 38,0 2600 220 0,320 233 232
3x120 rm 42,0 3100 230 0,253 266 270
3x150 rm 47,0 3850 240 0,206 299 308
3x185 rm 52,0 4650 250 0,164 340 357
3x240 rm 57,0 5500 240* 0,125 401 435
3x300 rm 63,0 6850 250* 0,100 455 501
3x400 rm 73,0 8650 260* 0,0778 526 592
rm:Stranded conductor, * For 500 m. Cable