0,6/1 kV XLPE INSULATED WITH PVC OUTER SHEATH ALUMINUM CONDUCTOR MULTICORE POWER CABLES
0,6/1 kV  XLPE INSULATED WITH PVC OUTER SHEATH ALUMINUM CONDUCTOR MULTICORE POWER CABLES

0,6/1 kV XLPE INSULATED WITH PVC OUTER SHEATH ALUMINUM CONDUCTOR MULTICORE POWER CABLES

• YAXV-R
• NA2XY

Öznur icon
Code YAXV-R, NA2XY
Standarts TS IEC 60502-1, VDE 0276
Construction Aluminum Conductor, XLPE insulation, PVC outer Steath
Application These cables with very low dielectric losses are used in power plants, in the residential and industrial areas, underground internal / external and in cable ducts where there is sudden load changes.
Technical Datas Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
Weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(maks.) resistance
at 
20 °C (maks.)
 
Current carrying capacity
(approx.)
(mm²) (mm) (kg/km) (cm) (ohm/km) Ground(A)
at 20°C
Air(A)
at 30°C
2x25 rm 21,0 550 130 1,200 - 91
2x35 rm 23,0 750 130 0,868 - 113
2x50 rm 26,0 900 150 0,641 - 138
2x70 rm 30,0 1150 180 0,443 - 174
2x95 rm 33,0 1500 200 0,320 - 210
2x120 rm 37,0 1850 220 0,253 - 244
2x150 rm 41,0 2400 230 0,206 - 281
2x185 rm 46,0 2850 240 0,164 - 320
2x240 rm 50,0 3500 210* 0,125 - 378
rm:Stranded conductor, * For 500 m. Cable