• YAXV-R
• NA2XY
0,6/1 kV XLPE INSULATED WITH PVC OUTER SHEATH ALUMINUM CONDUCTOR MULTICORE POWER CABLES
0,6/1 kV XLPE INSULATED WITH PVC OUTER SHEATH ALUMINUM CONDUCTOR MULTICORE POWER CABLES
Code | YAXV-R, NA2XY |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Aluminum Conductor, XLPE insulation, PVC outer Steath |
Application | These cables with very low dielectric losses are used in power plants, in the residential and industrial areas, underground internal / external and in cable ducts where there is sudden load changes. |
Technical Datas | Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C Min. Bending Radius 12*D D:Cable Overall Diameter (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||
Nominal cross-section |
Overall Diameter |
Net Weight |
Delivery reel size for 1000 m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity (approx.) |
|
(mm²) | (mm) | (kg/km) | (cm) | (ohm/km) | Ground(A) at 20°C |
Air(A) at 30°C |
4x25 rm | 24,0 | 800 | 140 | 1,200 | 111 | 100 |
4x35 rm | 26,5 | 950 | 150 | 0,868 | 132 | 122 |
4x50 rm | 30,0 | 1300 | 160 | 0,641 | 157 | 147 |
4x70 rm | 35,0 | 1700 | 200 | 0,443 | 195 | 189 |
4x95 rm | 39,0 | 2150 | 220 | 0,320 | 233 | 232 |
4x120 rm | 43,0 | 2700 | 230 | 0,253 | 266 | 270 |
4x150 rm | 49,0 | 3400 | 240 | 0,206 | 299 | 308 |
4x185 rm | 54,0 | 4100 | 250 | 0,164 | 340 | 357 |
4x240 rm | 60,5 | 5250 | 230* | 0,125 | 401 | 435 |
4x300 rm | 66,0 | 6450 | 240* | 0,100 | 455 | 501 |
4x400 rm | 74,0 | 8900 | 250* | 0,0778 | 526 | 592 |