20,3/35 KV XLPE INSULATED GALVANIZED ROUND STEEL WIRE ARMOURED MEDIUM VOLTAGE POWER CABLES
20,3/35 KV XLPE INSULATED GALVANIZED ROUND STEEL WIRE ARMOURED MEDIUM VOLTAGE POWER CABLES

20,3/35 KV XLPE INSULATED GALVANIZED ROUND STEEL WIRE ARMOURED MEDIUM VOLTAGE POWER CABLES

• YXC8VZ2V-R
• N2XSEYRY

Öznur icon
Code YXC8VZ2V-R, N2XSEYRY
Standarts TS IEC 60502-2, TSE K 204, Teknik Şartname, VDE 0276
Construction Copper conductor, Inner semiconductive layer, XLPE insulation, Outer semiconductive layer, Semiconductive tape, Copper shield, PVC fill, PVC seperation sheath, Galvanized flat steel wire armor, Galvanized steel wires and tape,PVC outer sheath
Application Where there is mechanical heavy duties,underground,cable ducts, power distribution cabinets,city network,industrial builts
Technical Datas Max. operating temperature 90 ° C
Max. permissible short circuit temperature 250 °C, max. for 5 sec.
Min. Bending radius 15*D D: overall diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
weight
Standart 
delivery 
lenght
Standart 
delivery
reel size
Conductor DC 
resistance 
at 20 ° C
Per conductor 
inductance 
(approx.)
Operating
apacitance 
(approx.) at 20 °C
  Current carrying capacity 
(approx.)
  (mm²)   (mm)   (kg/km)   (m)   (cm)   (ohm/km)   (mH/km) (mikrofarad/km) Ground (A)
at
20 °C
Air (A)
at 30 °C
3x35/16 rm 84,0 11600 500 240 0,524 0,47 0,11 175 172
3x50/16 rm 87,0 12600 500 260 0,387 0,45 0,12 205 205
3x70/16 rm 91,0 14000 500 260 0,268 0,42 0,13 252 253
3x95/16 rm 95,0 15600 350 240 0,193 0,40 0,15 305 307
3x120/16 rm 99,0 17000 350 260 0,153 0,39 0,16 350 352
3x150/25 rm 102,0 18800 350 260 0,124 0,37 0,17 392 397
3x185/25 rm 107,0 20800 300 240 0,0991 0,36 0,18 445 453
3x240/25 rm 113,0 23600 250 240 0,0754 0,35 0,20 520 529
3x300/25 rm 118,0 26650 250 260 0,0601 0,29 0,22 580 626
3x400/35 rm 125,0 30950 250 260 0,0470 0,28 0,24 650 720
rm:Stranded conductor