3,6/6-20,3/35 kV Aluminum Conductor XLPE Medium Voltage Cables
24 type products.
![3,6/6 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321143301078.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![6/10 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321143128498.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![8,7/15 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321142544558.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![12/20 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321142444078.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![18/30 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321142327978.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![20,3/35 kV XLPE INSULATED WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321142152838.jpg)
Code : YAXC7V-R (TSE), NA2XSY(VDE), 2AXSY(IEC), Al/XLPE/SC/PVC (BS)
Standarts : TS IEC 60502-2, TSE K 204, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, TSE K 204, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7V-R, NA2XSY, 2AXSY
![3,6/6 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321141223418.jpg)
Code : YAXC7VY2V-R (TSE), NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![6/10 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018431334545688.jpg)
Code : YAXC7VY2V-R (TSE),NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![8,7/15 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114024408.jpg)
Code : YAXC7VY2V-R (TSE),NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![12/20 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114012738.jpg)
Code : YAXC7VY2V-R (TSE), NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![18/30 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/20183211359223068.jpg)
Code : YAXC7VY2V-R (TSE),NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![20,3/35 kV XLPE INSULATED, ROUNDED ALUMINUM ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/20183211358558068.jpg)
Code : YAXC7VY2V-R (TSE),NA2XSYR(AL)Y (VDE), Al/XLPE/SC/PVC/AWA/PVC (BS)
Standarts : TS IEC 60502-2, TSE K 204, Teknik şartname, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-2, TSE K 204, Teknik şartname, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield, Copper Helix Tape, Polyester Tape, PVC Separator Sheath, Aluminum Rounded Rod Shield, Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC7VY2V-R, NA2XSYR(AL)Y
![3,6/6 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114987568.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, Teknik Şartname, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Industrial facilities, Underground cable channels
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Teknik Şartname, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Industrial facilities, Underground cable channels
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![6/10 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321148374608.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![8,7/15 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321148249288.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![12/20 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321147587228.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![18/30 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321147403148.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![20,3/35 kV XLPE INSULATED, FLAT STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321147152318.jpg)
Code : YAXC8VZ3V-R (TSE), NA2XSEYFGbY(VDE)
Standarts : TSE IEC 60502-2, TSE K 204, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, TSE K 204, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Flat Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ3V-R, NA2XSEYFGbY
![3,6/6 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114674518.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp 250°C, For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY
![6/10 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321145544968.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY
![8,7/15 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114539138.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY
![12/20 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321144435748.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY
![18/30 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/2018321144281528.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp. 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY
![20,3/35 kV XLPE INSULATED, ROUNDED STEEL ROD SHIELD WITH ALUMINUM CONDUCTOR, SINGLE CORE MEDIUM VOLTAGE POWER CABLES](/upl/201832114489418.jpg)
Code : YAXC8VZ2V-R, NA2XSEYRY
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TSE IEC 60502-2, Technical Specs, VDE 0276
Construction : Aluminum Conductor, Inner semi-conductor, XLPE insulation, Outer Semi-Conductor, Semi-Conductor Tape, Copper Shield , PVC Filler, PVC Separator Sheath, Galvanized Rounded Steel Rod Shield, Galvanized Steel Helix Tape, PVC Outer Sheath
Application : Used in Under heavy operating conditions and mechanical stres, Underground, Power centers, Switchgear, City networks, Industrial facilities, Underground and cable channel.
Technical Datas : Max. Operating Temp. 90°C
Max. Short Circuit Temp 250°C , For Max. 5 Sec
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAXC8VZ2V-R, NA2XSEYRY