• AAC
STRANDED ALUMINUM CONDUCTORS FOR AERIAL LINES (AAC)
STRANDED ALUMINUM CONDUCTORS FOR AERIAL LINES (AAC)
Code | AAC |
Standarts | TS EN 50182, TEDAŞ-MYD 96/014 |
Construction | Uninsulated stranded aluminum conductor |
Application | Used in areas not available for underground cable transmission, in open areas where the cost of using underground cables is high, at low voltage aerial lines. |
Technical Datas |
- Product Description
Nominal Cross Section |
Canadian Standards |
Cross Section For Whole Conductor |
Copper Equivalent |
Number of Rods and Diameters | Diameter For Whole Conductor | Nom. Tensile Strength | Conductor DC (Max.) Resistance at 20°C | Net Weight | ||
mm² | Type | Section | mm² | mm² | Num | Dia. | kg | ohm/km | kg/km | |
21 | Rose | 4 | 21.14 | 13.30 | 7 | 1.96 | 5,88 | 416 | 1,3558 | 57,8 |
27 | Lily | 3 | 26.60 | 16.73 | 7 | 2.20 | 6,60 | 514 | 1,0776 | 72,8 |
34 | İris | 2 | 33.53 | 21.09 | 7 | 2.47 | 7,41 | 637 | 0,8537 | 91,8 |
42 | Pansy | 1 | 42.49 | 26.72 | 7 | 2.78 | 8,34 | 777 | 0,6743 | 116,4 |
53 | Popy | 1/10 | 53.48 | 33.63 | 7 | 3.12 | 9,36 | 941 | 0,5354 | 146,4 |
67 | Aster | 2/0 | 67.14 | 42.22 | 7 | 3.50 | 10,50 | 1185 | 0,4254 | 184,4 |
85 | Phlox | 3/0 | 84.91 | 53.40 | 7 | 3.93 | 11,79 | 1435 | 0,3372 | 232,5 |
107 | Oxlip | 4/0 | 107.38 | 67.53 | 7 | 4.42 | 13,26 | 1814 | 0,2662 | 294,0 |
126 | Valerian | 250000 | 126.35 | 79.46 | 19 | 2.91 | 14,55 | 2261 | 0,2277 | 347,5 |
135 | Daisy | 266800 | 135.28 | 85.07 | 19 | 3.01 | 15,05 | 2421 | 0,2127 | 371,1 |
152 | Peony | 300000 | 151.81 | 95.47 | 19 | 3.19 | 15,85 | 2671 | 0,1896 | 417,2 |