• STRANDED HARD DRAWN COPPER CONDUCTORS FOR
STRANDED HARD DRAWN COPPER CONDUCTORS FOR OVERHEAD LINES
STRANDED HARD DRAWN COPPER CONDUCTORS FOR OVERHEAD LINES
Code | Stranded hard drawn copper conductors for Overhead lines |
Standarts | TS 3 |
Construction | Stranded copper conductors are produced by stranding of hard copper wires to obtain maximum tensile strenght in accordance with TS 3 Standart.Each round wire are produce according to the TS 2 standart. |
Application | This conductors is used in Over Head lines. |
Technical Datas | This conductors is used in Over Head lines. |
- Product Description
Dimensions and Weights
|
Electrical Information
|
||||
Nominal
Cross section |
Number Of
Wire/wire Dia |
Overall
diameter approx |
Net weight
approx. |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Calculated Min.
Break Strength |
mm² | Wire diameter |
mm
|
kg/km
|
ohm/km
|
kN.
|
10 rm
|
7/1.32
|
3,96
|
85,8
|
1,915
|
3,96
|
16 rm
|
7/1.70
|
5,10
|
142,4
|
1,154
|
6,50
|
25 rm
|
7/2.12
|
6,36
|
221,4
|
0,742
|
9,99
|
35 rm
|
7/2.50
|
7,50
|
308,0
|
0,534
|
13,91
|
50 rm
|
7/3.00
|
9,00
|
443,5
|
0,369
|
19,57
|
50 rm
|
19/1.80
|
9,00
|
436,3
|
0,384
|
19,36
|
70 rm
|
19/2.12
|
10,60
|
605,2
|
0,275
|
26,55
|
95 rm
|
19/2.50
|
12,50
|
841,7
|
0,198
|
36,93
|
120 rm
|
19/2.80
|
14,00
|
1056,0
|
0,158
|
45,27
|
150 rm
|
37/2.24
|
15,68
|
1320,0
|
0,127
|
57,73
|
185 rm
|
37/2.50
|
17,50
|
1644,0
|
0,102
|
71,91
|
240 rm
|
61/2.24
|
20,20
|
2179,0
|
0,077
|
95,17
|
300 rm
|
61/2.50
|
22,55
|
2715,0
|
0,062
|
118,56
|