STRANDED HARD DRAWN COPPER CONDUCTORS FOR OVERHEAD LINES
STRANDED HARD DRAWN COPPER CONDUCTORS FOR OVERHEAD LINES

STRANDED HARD DRAWN COPPER CONDUCTORS FOR OVERHEAD LINES

• STRANDED HARD DRAWN COPPER CONDUCTORS FOR

Öznur icon
Code Stranded hard drawn copper conductors for Overhead lines
Standarts TS 3
Construction Stranded copper conductors are produced by stranding of hard copper wires to obtain maximum tensile strenght in accordance with TS 3 Standart.Each round wire are produce according to the TS 2 standart.
Application This conductors is used in Over Head lines.
Technical Datas This conductors is used in Over Head lines.
  • Product Description
Dimensions and Weights
Electrical Information
 Nominal
Cross section
Number Of
Wire/wire Dia
Overall
diameter approx
Net weight
approx.
Conductor DC (maks.)
resistance at 20 °C (maks.)
Calculated Min.
Break Strength
mm²  Wire diameter
mm
kg/km
ohm/km
kN.
10 rm
7/1.32
3,96
85,8
1,915
3,96
16 rm
7/1.70
5,10
142,4
1,154
6,50
25 rm
7/2.12
6,36
221,4
0,742
9,99
35 rm
7/2.50
7,50
308,0
0,534
13,91
50 rm
7/3.00
9,00
443,5
0,369
19,57
50 rm
19/1.80
9,00
436,3
0,384
19,36
70 rm
19/2.12
10,60
605,2
0,275
26,55
95 rm
19/2.50
12,50
841,7
0,198
36,93
120 rm
19/2.80
14,00
1056,0
0,158
45,27
150 rm
37/2.24
15,68
1320,0
0,127
57,73
185 rm
37/2.50
17,50
1644,0
0,102
71,91
240 rm
61/2.24
20,20
2179,0
0,077
95,17
300 rm
61/2.50
22,55
2715,0
0,062
118,56
 rm : Stranded conductor