• YAVV-R (TSE)
• NAYY (VDE)
• AL/PVC/PVC (BS)
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR POWER CABLES
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR POWER CABLES
Code | YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS) |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Aluminum Conductor, PVC insulated, PVC Outer Sheath |
Application | Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable. |
Technical Datas | Max. Operating Temp. 70 °C
Max. Short Circuit Temp Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C Min. Bending Radius 12*D D:Cable Overall Diameter (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||
Nominal cross-section |
Overall Diameter |
Net weight |
Delivery reel size for 1000 m cable |
Conductor DC (max.) resistance at 20 °C (max.) |
Current carrying capacity (approx.) |
|
(mm²) | (mm) | (kg/km) | (cm) | (ohm/km) | Ground (A) at 20 °C |
Air (A) at 30 °C |
3x25 rm | 23,0 | 720 | 130 | 1,200 | 99 | 83 |
3x35 rm | 26,0 | 900 | 140 | 0,868 | 118 | 102 |
3x50 rm | 30,0 | 1200 | 160 | 0,641 | 142 | 124 |
3x70 rm | 33,0 | 1520 | 180 | 0,443 | 176 | 158 |
3x95 rm | 38,0 | 2000 | 210 | 0,320 | 211 | 190 |
3x120 rm | 42,0 | 2400 | 210 | 0,253 | 242 | 221 |
3x150 rm | 45,0 | 3100 | 230 | 0,206 | 270 | 252 |
3x185 rm | 50,0 | 3700 | 240 | 0,164 | 308 | 289 |
3x240 rm | 57,0 | 4700 | 220* | 0,125 | 363 | 339 |
3x300 rm | 63,0 | 6000 | 230* | 0,100 | 412 | 377 |
3x400 rm | 71,0 | 7750 | 240* | 0,0778 | 475 | 444 |