0,6/1 KV Aluminum Conductor Low Voltage Cables
11 type products.
Code : YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² Cross S. 160°C >300 mm² 140°C
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² Cross S. 160°C >300 mm² 140°C
Min. Bending Radius 15*D D:Cable Overall Diameter (mm)
YAVV-R, NAYY, AL/PVC/PVC
Code : YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable
Technical Datas : Max. Operating Temp.70 °C
Max. Short Circuit Temp.160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable
Technical Datas : Max. Operating Temp.70 °C
Max. Short Circuit Temp.160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVV-R, NAYY, AL/PVC/PVC
Code : YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVV-R, NAYY, AL/PVC/PVC
Code : YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVV-R, NAYY, AL/PVC/PVC
Code : YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Outer Sheath
Application : Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVV-R, NAYY, AL/PVC/PVC
Code : YAVC7V-R (TSE), NAYCY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application : Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application : Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVC7V-R, NAYCY
Code : YAVZ3V-R (TSE),NAYFGbY (VDE)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² için 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² için 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVZ3V-R, NAYFGbY
Code : YAVZ3V-R (TSE),NAYFGbY (VDE)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVZ3V-R, NAYFGbY
Code : YAVZ2V-R, NAYRY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Round Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Round Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVZ2V-R, NAYRY
Code : YAVZ2V-R (TSE), NAYRY (VDE)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Round Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. 160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Round Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application : It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions.
Technical Datas : Max. Operating Temp. 70 °C
Max. Short Circuit Temp. 160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVZ2V-R, NAYRY
Code : YAVC7V-R, NAYCY
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application : Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas : Max. Operating Temp. 70°C
Max. Short Circuit Temp 160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application : Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas : Max. Operating Temp. 70°C
Max. Short Circuit Temp 160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
YAVC7V-R, NAYCY