0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES
0,6/1 kV  PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES

0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES

• YAVC7V-R
• NAYCY

Öznur icon
Code YAVC7V-R, NAYCY
Standarts TS IEC 60502-1, VDE 0276
Construction Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas Max. Operating Temp. 70°C
Max. Short Circuit Temp 160°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(max.) resi
stance at 
20 °C (max.)
 
  Current carrying capacity
(approx.)
 
  (mm²)
 
  (mm)
 
  (kg/km)
 
  (cm)
 
  (ohm/km)
Ground (A)
at 20°C
Air (A)
at 30°C
   
1x25/16 rm 16,0 400 140 1,200 125 105 87 75
1x35/16 rm 17,0 450 160 0,868 151 127 131 113
1x50/25 rm 19,5 630 160 0,641 179 151 160 138
1x70/35 rm 21,5 800 200 0,443 218 186 202 174
1x95/50 rm 24,0 1050 210 0,320 261 223 249 210
1x120/70 rm 26,0 1350 220 0,253 297 254 291 244
1x150/70 rm 27,5 1500 230 0,206 332 285 333 271
1x185/95 rm 30,5 1900 240 0,164 376 323 384 320
1x240/120 rm 33,5 2350 250 0,125 437 378 460 378
rm:Stranded conductor