• YAVC7V-R
• NAYCY
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES
Code | YAVC7V-R, NAYCY |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath |
Application | Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment. |
Technical Datas | Max. Operating Temp. 70°C
Max. Short Circuit Temp 160°C Min. Bending Radius 12*D D:Cable Overall Diameter (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||||
Nominal cross-section |
Overall Diameter |
Net weight |
Delivery reel size for 1000 m cable |
Conductor DC (max.) resistance at 20 °C (max.) |
Current carrying capacity (approx.) |
|||
|
|
|
|
|
Ground (A) at 20°C |
Air (A) at 30°C |
||
••• | ••• | |||||||
1x25/16 rm | 16,0 | 400 | 140 | 1,200 | 125 | 105 | 87 | 75 |
1x35/16 rm | 17,0 | 450 | 160 | 0,868 | 151 | 127 | 131 | 113 |
1x50/25 rm | 19,5 | 630 | 160 | 0,641 | 179 | 151 | 160 | 138 |
1x70/35 rm | 21,5 | 800 | 200 | 0,443 | 218 | 186 | 202 | 174 |
1x95/50 rm | 24,0 | 1050 | 210 | 0,320 | 261 | 223 | 249 | 210 |
1x120/70 rm | 26,0 | 1350 | 220 | 0,253 | 297 | 254 | 291 | 244 |
1x150/70 rm | 27,5 | 1500 | 230 | 0,206 | 332 | 285 | 333 | 271 |
1x185/95 rm | 30,5 | 1900 | 240 | 0,164 | 376 | 323 | 384 | 320 |
1x240/120 rm | 33,5 | 2350 | 250 | 0,125 | 437 | 378 | 460 | 378 |