0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES

0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND COPPER CONSANTRIC SHIELD POWER CABLES

• YAVC7V-R (TSE)
• NAYCY (VDE)

Öznur icon
Code YAVC7V-R (TSE), NAYCY (VDE)
Standarts TS IEC 60502-1, VDE 0276
Construction Aluminum Conductor, PVC insulated, PVC Filler, Copper Consantric Shield, Copper Tape Helix, PVC Outer Sheath
Application Generally, these concentric conductors, which are used underground in the settlement areas, open the switch or the fuse connected to the network during any mechanical impact and prevent energy damage to the environment.
Technical Datas Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(max.) resistance

at 20 °C (max.)
 
  Current carrying capacity 
(approx.)

 
(mm²) (mm) (kg/km) (cm) (ohm/km) Ground (A)
at 20°C
Air (A)
at 30°C
3x25/16 rm 26,0 900 140 1,200 99 83
3x35/16 rm 29,0 1100 160 0,868 118 102
3x50/25 rm 32,0 1500 160 0,641 142 124
3x70/35 rm 37,0 2000 200 0,443 176 158
3x95/50 rm 42,0 2650 210 0,320 211 190
3x120/70 rm 45,0 3250 230 0,253 242 221
3x150/70 rm 50,0 3850 240 0,206 270 252
3x185/95 rm 55,0 4850 250 0,164 308 289
3x240/120 rm 63,0 6100 230* 0,125 363 339
3x300/150 rm 69,0 7450 240* 0,100 412 377
3x400/185 rm 77,0 9600 250* 0,0778 475 444
rm:Stranded conductor, * For 500 m. Cable