0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND STEEL SHIELD POWER CABLES
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND STEEL SHIELD POWER CABLES

0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR AND STEEL SHIELD POWER CABLES

• YAVZ3V-R (TSE)
• NAYFGbY (VDE)

Öznur icon
Code YAVZ3V-R (TSE),NAYFGbY (VDE)
Standarts TS IEC 60502-1, VDE 0271
Construction Aluminum Conductor, PVC Insulation, PVC Filler, Galvanized Flat Steel, Galvanized Steel Helix Tape, PVC Outer Shield
Application It is used internally/externally under soil and in cable ducts as mechanical forcings are suitable for durable and heavy operating conditions
Technical Datas Max. Operating Temp. 70 °C
Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² için 140°C
Min. Bending Radius 12*D D:Cable Overall Diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
  Nominal 
cross-section
Overall 
Diameter
  Net 
weight
Delivery 
reel size for 
1000 m cable
Conductor DC 
(max.) resistance
at 
20 °C (max.)
  Current carrying capacity 
(approx.)

 
(mm²) (mm) (kg/km) (cm) (ohm/km) Ground (A)
at 20°C
Air (A) at
30°C
3x25/16 rm 28,0 1350 160 1,200 99 83
3x35/16 rm 31,0 1550 160 0,868 118 102
3x50/25 rm 35,0 2000 180 0,641 142 124
3x70/35 rm 38,0 2500 210 0,443 176 158
3x95/50 rm 44,0 3100 230 0,320 211 190
3x120/70 rm 48,0 3550 240 0,253 242 221
3x150/70 rm 51,0 4300 250 0,206 270 252
3x185/95 rm 56,0 5100 220* 0,164 308 289
3x240/120 rm 63,0 6250 230* 0,125 363 339
3x300/150 rm 70,0 7800 240* 0,100 412 377
3x400/185 rm 77,0 9900 230** 0,0778 475 444