0.6/1 kV PVC INSULATED CABLES WITH COPPER CONDUCTOR
0.6/1 kV PVC INSULATED CABLES WITH COPPER CONDUCTOR

0.6/1 kV PVC INSULATED CABLES WITH COPPER CONDUCTOR

• YVV(TSE)
• NYY(VDE)
• Cu/PVC/PVC(BS)

Öznur icon
Code YVV-U(TSE), NYY (VDE), Cu/PVC/PVC (BS)
Standarts TS IEC 60502-1, VDE 0271
Construction Copper conductor, PVC insulation,PVC filler, PVC outer sheath
Application Indoors and outdoors, in cable ducts, underground, in power and switching stations, industrial plants, where there is no risk of mechanical damage.
Technical Datas Max. Operating temperature 70 °C
Max. Short circuit temperature 160 °C
Min. Bending radius 12*D D:Cable outer diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
 
Nominal
cross-section
 
Overall
Diameter 
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.)
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
5x1.5 re
13,0
235
90
12,1
27
19
7x1.5 re
14,0
290
90
12,1
16
12
10x1.5 re
17,0
400
110
12,1
13
10
12x1.5 re
17,5
440
110
12,1
12
10
14x1.5 re
18,0
495
110
12,1
12
9
19x1.5 re
20,0
630
120
12,1
10
8
21x1.5 re
21,0
700
120
12,1
10
8
24x1.5 re
23,0
800
130
12,1
9
7
30x1.5 re
25,0
950
140
12,1
9
7
40x1.5 re
28,0
1200
150
12,1
8
7
48x1.5 re
31,0
1400
160
12,1
7
6
61x1.5 re
33,0
1800
180
12,1
7
6
5x2.5 re
14,0
310
100
7,41
36
25
7x2.5 re
16,0
390
100
7,41
20
16
10x2.5 re
19,5
520
120
7,41
17
14
12x2.5 re
20,0
600
120
7,41
16
13
14x2.5 re
21,0
680
120
7,41
15
13
19x2.5 re
23,0
860
130
7,41
14
11
21x2.5 re
24,0
950
150
7,41
13
11
24x2.5 re
27,0
1080
160
7,41
12
10
30x2.5 re
29,0
1300
160
7,41
11
9
40x2.5 re
33,0
1700
180
7,41
10
9
48x2.5 re
35,0
2000
210
7,41
10
8
61x2.5 re
39,0
2500
220
7,41
9
8
re: Single-wire conductor