0.6/1 kV PVC INSULATED MULTI CORE CABLES WITH COPPER CONDUCTOR
0.6/1 kV PVC INSULATED MULTI CORE CABLES WITH COPPER CONDUCTOR

0.6/1 kV PVC INSULATED MULTI CORE CABLES WITH COPPER CONDUCTOR

• YVV(TSE)
• NYY(VDE)
• Cu/PVC/PVC(BS)

Öznur icon
Code YVV-R (TSE), NYY (VDE), Cu/PVC/PVC (BS)
Standarts TS IEC 60502-1, VDE 0276
Construction Copper conductor, PVC insulation,PVC filler, PVC outer sheath
Application Preferably for installation indoors, in cable ducts and in industrial plants or switching stations underground installation with additional protection where mechanical damage is unexpected.
Technical Datas Max. Operating temperature 70 °C
Max. Short circuit temperature <=300 mm² for 160 °C > 300 mm² for 140 °C
Min. Bending radius 12*D D:Cable outer diameter (mm)
  • Product Description
Dimensions and Weights Electrical Information
 
Nominal 
cross-section
 
Overll
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C  (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
3x16/10 rm
21,5
900
130
1,15
102
79
3x25/16 rm
24,5
1350
140
0,727
133
100
3x35/16 rm
26,5
1700
150
0,524
159
125
3x50/25 rm
31,0
2250
160
0,387
188
153
3x70/35 rm
34,5
3050
200
0,268
232
195
3x95/50 rm
40,0
4050
220
0,193
280
238
3x120/70 rm
43,0
5150
230
0,153
318
275
3x150/70 rm
47,5
6050
240
0,124
359
320
3x185/95 rm
52,5
7750
210*
0,0991
406
364
3x240/120 rm
59,0
9800
230*
0,0754
473
430
3x300/150 rm
66,0
12700
250*
0,0601
535
510
3x400/185 rm
74,0
16000
220**
0,0470
613
595
rm:Stranded conductor, * For 500 m. Cable, ** For 250 m. Cable