• YVV(TSE)
• NYY(VDE)
• Cu/PVC/PVC(BS)
0.6/1 kV PVC INSULATED MULTI CORE CABLES WITH COPPER CONDUCTOR
0.6/1 kV PVC INSULATED MULTI CORE CABLES WITH COPPER CONDUCTOR
Code | YVV-R (TSE), NYY (VDE), Cu/PVC/PVC (BS) |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Copper conductor, PVC insulation,PVC filler, PVC outer sheath |
Application | Preferably for installation indoors, in cable ducts and in industrial plants or switching stations underground installation with additional protection where mechanical damage is unexpected. |
Technical Datas | Max. Operating temperature 70 °C
Max. Short circuit temperature <=300 mm² for 160 °C > 300 mm² for 140 °C Min. Bending radius 12*D D:Cable outer diameter (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||
cross-section |
Diameter |
|
Delivery reel size for 1000m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity in | |
|
|
|||||
mm²
|
mm
|
kg/km
|
cm
|
ohm/km
|
||
3x16/10 rm
|
21,5
|
900
|
130
|
1,15
|
102
|
79
|
3x25/16 rm
|
24,5
|
1350
|
140
|
0,727
|
133
|
100
|
3x35/16 rm
|
26,5
|
1700
|
150
|
0,524
|
159
|
125
|
3x50/25 rm
|
31,0
|
2250
|
160
|
0,387
|
188
|
153
|
3x70/35 rm
|
34,5
|
3050
|
200
|
0,268
|
232
|
195
|
3x95/50 rm
|
40,0
|
4050
|
220
|
0,193
|
280
|
238
|
3x120/70 rm
|
43,0
|
5150
|
230
|
0,153
|
318
|
275
|
3x150/70 rm
|
47,5
|
6050
|
240
|
0,124
|
359
|
320
|
3x185/95 rm
|
52,5
|
7750
|
210*
|
0,0991
|
406
|
364
|
3x240/120 rm
|
59,0
|
9800
|
230*
|
0,0754
|
473
|
430
|
3x300/150 rm
|
66,0
|
12700
|
250*
|
0,0601
|
535
|
510
|
3x400/185 rm
|
74,0
|
16000
|
220**
|
0,0470
|
613
|
595
|