• YXC7V
• N2XCY
0.6/1 kV XLPE INSULATED CONCENTRIC WIRE SCREENED PVC SHEATHED WITH COPPER CONDUCTOR
0.6/1 kV XLPE INSULATED CONCENTRIC WIRE SCREENED PVC SHEATHED WITH COPPER CONDUCTOR
Code | YXC7V, N2XCY |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Copper Conductor, XLPE Insulation ,PVC Filler , Copper wires screen,Copper tape, PVC Outer Sheath. |
Application | These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts. |
Technical Datas | Max. operating temperature 90 °C
Max. short circuit temperature 250 °C Min. Bending radius 12*D D: Cable overall Dia. (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||
cross-section |
Diameter |
|
Delivery reel size for 1000m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity in
|
|
|
|
|||||
mm²
|
mm
|
kg/km
|
cm
|
ohm/km
|
||
3x10/10 rm
|
19,0
|
700
|
120
|
1,83
|
86
|
73
|
3x16/16 rm
|
21,0
|
920
|
130
|
1,15
|
111
|
98
|
3x25/16 rm
|
25,0
|
1300
|
140
|
0,727
|
143
|
126
|
3x35/16 rm
|
27,0
|
1650
|
160
|
0,524
|
173
|
156
|
3x50/25 rm
|
31,0
|
2220
|
160
|
0,387
|
205
|
190
|
3x70/35 rm
|
36,0
|
3100
|
200
|
0,268
|
252
|
245
|
3x95/50 rm
|
41,0
|
4200
|
230
|
0,193
|
303
|
297
|
3x120/70 rm
|
44,0
|
5200
|
240
|
0,153
|
346
|
346
|
3x150/70 rm
|
48,0
|
6100
|
210*
|
0,124
|
390
|
398
|
3x185/95 rm
|
54,0
|
7900
|
220*
|
0,0991
|
441
|
455
|
3x240/120 rm
|
60,0
|
9950
|
240*
|
0,0754
|
511
|
535
|