0.6/1 kV Low Voltage XLPE Insulated Power Cables
14 type products.
Code : YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation , PVC outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 15*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation , PVC outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 15*D D: Cable overall Dia. (mm)
YXV-U, YXV-R, N2XY
Code : YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXV-U, YXV-R, N2XY
Code : YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation, PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation, PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXV-U, YXV-R, N2XY
Code : YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXV-U, YXV-R, N2XY
Code : YXV-R (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXV-R, N2XY
Code : YXZ3V, N2XFGBY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ3V, N2XFGBY
Code : YXZ3V, N2XFGBY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ3V, N2XFGBY
Code : YXZ3V, N2XFGBY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ3V, N2XFGBY
Code : YXY2V, N2XR(A)Y
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation , PVC Filler, Aluminum Round Wire, PP retaining band, PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation , PVC Filler, Aluminum Round Wire, PP retaining band, PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXY2V, N2XR(A)Y
Code : YXZ2V, N2XRY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ2V, N2XRY
Code : YXZ2V, N2XRY
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ2V, N2XRY
Code : YXZ2V-U, YXZ2V-R (TSE), N2XRY (VDE)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0271
Construction : Copper Conductor, XLPE Insulation, PVC Filler,Galvanized round steel wire, Galvanized steel tape,PVC Outer Sheath
Application : These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXZ2V-U, YXZ2V-R, N2XRY
Code : YXV-U (TSE), N2XY (VDE)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation,PVC filler, PVC Outer Sheath
Application : Is used as control cable in Power stations and factories where signaling is required. Can be laid indoors, outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation,PVC filler, PVC Outer Sheath
Application : Is used as control cable in Power stations and factories where signaling is required. Can be laid indoors, outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXV-U, N2XY
Code : YXC7V, N2XCY
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler , Copper wires screen,Copper tape, PVC Outer Sheath.
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
Standarts : TS IEC 60502-1, VDE 0276
Construction : Copper Conductor, XLPE Insulation ,PVC Filler , Copper wires screen,Copper tape, PVC Outer Sheath.
Application : These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas : Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
YXC7V, N2XCY