0.6/1 kV XLPE INSULATED FLAT STEEL WIRE ARMOURED PVC SHEATHED WITH COPPER CONDUCTOR
0.6/1 kV XLPE INSULATED FLAT STEEL WIRE ARMOURED PVC SHEATHED WITH COPPER CONDUCTOR

0.6/1 kV XLPE INSULATED , FLAT STEEL WIRE ARMOURED , PVC SHEATHED WITH COPPER CONDUCTOR

• YXZ3V
• N2XFGBY

Öznur icon
Code YXZ3V, N2XFGBY
Standarts TS IEC 60502-1, VDE 0271
Construction Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights
Electrical Information
 
Nominal 
cross-section
 
Overall
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
3x16/10 rm
22,0
1200 140 1,15
111
98
3x25/16 rm
25,0
1650 150 0,727
143
126
3x35/16 rm
27,0
2000 160 0,524
173
156
3x50/25 rm
31,0
2650 180 0,387
205
190
3x70/35 rm
35,5
3550 210 0,268
252
245
3x95/50 rm
39,5
4600 230 0,193
303
297
3x120/70 rm
44,0
5800 240 0,153
346
346
3x150/70 rm
48,0
6750 240 0,124
390
398
3x185/95 rm
53,0
8500 220* 0,0991
441
455
3x240/120 rm
58,0
10600 240* 0,0754
511
535
3x300/150 rm
65,0
13600 220** 0,0601
580
630
3x400/185 rm
75,0
17000 240** 0,0470
663
740
rm:Stranded conductor, * For 500 m lenght cables, ** For 250 m lenght cables