0.6/1 kV XLPE INSULATED FLAT STEEL WIRE ARMOURED PVC SHEATHED WITH COPPER CONDUCTOR
0.6/1 kV XLPE INSULATED FLAT STEEL WIRE ARMOURED PVC SHEATHED WITH COPPER CONDUCTOR

0.6/1 kV XLPE INSULATED FLAT STEEL WIRE ARMOURED PVC SHEATHED WITH COPPER CONDUCTOR

• YXZ3V
• N2XFGBY

Öznur icon
Code YXZ3V, N2XFGBY
Standarts TS IEC 60502-1, VDE 0271
Construction Copper Conductor, XLPE Insulation, PVC Filler,Galvanized flat steel wire, Galvanized steel tape,PVC Outer Sheath
Application These cables have a low dielectric loss, coupled with mechanical resistance are mainly used in energy networks with sudden load change residential or industrial areas.Can be laid outdoors,undergrounds and in areas where sudden mechanical stresses are expected.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights
Electrical Information
 
Nominal
cross-section
 
Overall
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
4x10 rm
21,0
1000
120
1,83
86
73
4x16 rm
23,0
1300
140
1,15
111
98
4x25 rm
26,5
1800
160
0,727
143
126
4x35 rm
30,0
2300
180
0,524
173
156
4x50 rm
33,0
2900
200
0,387
205
190
4x70 rm
37,5
4000
220
0,268
252
245
4x95 rm
41,5
5100
230
0,193
303
297
4x120 rm
46,5
6500
240
0,153
346
346
4x150 rm
52,0
7700
210*
0,124
390
398
4x185 rm
57,0
9700
220*
0,0991
441
455
4x240 rm
63,0
12000
240*
0,0754
511
535
4x300 rm
70,0
15300
240**
0,0601
580
630
4x400 rm
81,0
19750
260**
0,0470
663
740
5x10 rm
22,5
1100
120
1,83
86
73
5x16 rm
25,0
1450
140
1,15
111
98
5x25 rm
29,0
2020
160
0,727
143
126
5x35 rm
32,0
2600
180
0,524
173
156
5x50 rm
36,0
3300
200
0,387
205
190
5x70 rm
41,5
4450
220
0,268
252
245
5x95 rm
46,0
5700
230
0,193
303
297
5x120 rm
51,0
7100
240
0,153
346
346
5x150 rm
57,0
8600
210*
0,124
390
398
5x185 rm
63,0
10600
220*
0,0991
441
455
5x240 rm
70,0
13300
240*
0,0754
511
535
rm:Stranded conductor, * For 500 m lenght cables, ** For 250 m lenght cables