0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT MULTI CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES
0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT MULTI CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES

0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT MULTI CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES

• N2XH FE 180

Öznur icon
Code N2XH FE 180
Standarts TS HD 604 S1 , DIN - VDE 0276-604
Construction Copper Conductor, Mica Tape , XLPE Insulation , HFFR Filler , HFFR Outer Sheath
Application Used in energy networks in refineries,hotels,schools, mines, tunnels,high constructions,hospitals, power plants,data processing centers, business centers where there is a risk of fire.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights Electrical Information
 
Nominal
cross-section
 
Overall
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
3x16/10 rm
21,0
870
140 1,15
98
3x25/16 rm
24,5
1250 160 0,727
126
3x35/16 rm
26,5
1550 160 0,524
156
3x50/25 rm
30,0
2100 180 0,387
190
3x70/35 rm
34,0
2900 210 0,268
245
3x95/50 rm
38,0
3850 230 0,193
297
3x120/70 rm
43,0
5000 240 0,153
346
3x150/70 rm
46,5
5820 210* 0,124
398
3x185/95 rm
52,0
7400 220* 0,0991
455
3x240/120 rm
57,0
9420 240* 0,0754
535

rm:Stranded conductor, * For 500 m lenght cables