• N2XH FE 180
0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT MULTI CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES
0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT MULTI CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES
Code | N2XH FE 180 |
Standarts | TS HD 604 S1 , DIN - VDE 0276-604 |
Construction | Copper Conductor, Mica Tape , XLPE Insulation , HFFR Filler , HFFR Outer Sheath |
Application | Used in energy networks in refineries,hotels,schools, mines, tunnels,high constructions,hospitals, power plants,data processing centers, business centers where there is a risk of fire. |
Technical Datas | Max. operating temperature 90 °C
Max. short circuit temperature 250 °C Min. Bending radius 12*D D: Cable overall Dia. (mm) |
- Product Description
Dimensions and Weights | Electrical Information | ||||
cross-section |
Diameter |
|
Delivery reel size for 1000m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity in |
|
|||||
mm²
|
mm
|
kg/km
|
cm
|
ohm/km
|
|
3x1.5 re
|
11,5
|
180
|
100
|
12,1
|
23
|
3x2.5 re
|
12,5
|
230
|
100
|
7,41
|
32
|
3x4 re
|
13,5
|
280
|
110
|
4,61
|
42
|
3x6 re
|
14,5
|
360
|
110
|
3,08
|
53
|
3x10 rm
|
17,5
|
550
|
120
|
1,83
|
73
|
3x16 rm
|
19,5
|
750
|
120
|
1,15
|
98
|
3x25 rm
|
22,0
|
1050
|
130
|
0,727
|
126
|
3x35 rm
|
24,5
|
1400
|
150
|
0,524
|
156
|
3x50 rm
|
27,5
|
1800
|
160
|
0,387
|
190
|
3x70 rm
|
32,0
|
2550
|
180
|
0,268
|
245
|
3x95 rm
|
35,5
|
3400
|
210
|
0,193
|
297
|
3x120 rm
|
40,0
|
4350
|
220
|
0,153
|
346
|
3x150 rm
|
45,0
|
5250
|
240
|
0,124
|
398
|
3x185 rm
|
49,5
|
6600
|
200*
|
0,0991
|
455
|
3x240 rm
|
54,5
|
8400
|
220*
|
0,0754
|
535
|
re:Single-wire conductor, rm:Stranded conductor, * For 500 m lenght cables