• N2XH FE 180
0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT SINGLE CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES
0.6/1 kV XLPE INSULATED HALOJEN FREE FIRE RESISTANT SINGLE CORE WITH COPPER CONDUCTOR POWER SECURITY CABLES
Code | N2XH FE 180 |
Standarts | TS HD 604 S1 , DIN - VDE 0276-604 |
Construction | Copper Conductor, Mica Tape , XLPE Insulation , HFFR Outer Sheath |
Application | Used in energy networks in refineries,hotels,schools, mines, tunnels,high constructions,hospitals, power plants,data processing centers, business centers where there is a risk of fire. |
Technical Datas | Max. operating temperature 90 °C
Max. short circuit temperature 250 °C Min. Bending radius 15*D D: Cable overall Dia. (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||
cross-section |
Diameter |
|
Delivery reel size for 1000m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity in | |
Air(A) | ||||||
mm² | mm | kg/km | cm | ohm/km | ••• | |
1x4 re | 7,5 | 90 | 70 | 4,61 | 56 | 40 |
1x6 re | 8,0 | 110 | 70 | 3,08 | 71 | 53 |
1x10 rm | 9,5 | 160 | 80 | 1,83 | 100 | 74 |
1x16 rm | 10,0 | 220 | 80 | 1,15 | 135 | 100 |
1x25 rm | 11,5 | 320 | 90 | 0,727 | 180 | 133 |
1x35 rm | 12,5 | 420 | 90 | 0,524 | 225 | 167 |
1x50 rm | 14,0 | 530 | 90 | 0,387 | 273 | 205 |
1x70 rm | 16,0 | 740 | 110 | 0,268 | 350 | 265 |
1x95 rm | 17,5 | 950 | 110 | 0,193 | 428 | 325 |
1x120 rm | 19,0 | 1200 | 120 | 0,153 | 495 | 380 |
1x150 rm | 21,0 | 1450 | 130 | 0,124 | 575 | 442 |
1x185 rm | 23,0 | 1850 | 140 | 0,0991 | 660 | 510 |
1x240 rm | 25,5 | 2350 | 160 | 0,0754 | 780 | 605 |
1x300 rm | 28,5 | 3000 | 200 | 0,0601 | 864 | 690 |
1x400 rm | 32,0 | 3900 | 220 | 0,0470 | 1018 | 810 |
1x500 rm | 35,5 | 4900 | 240 | 0,0366 | 1173 | 930 |
re:Single-wire conductor , rm:Stranded conductor