• N2XH
0.6/1 kV XLPE INSULATED HALOJEN FREE FLAME RETARDANT MULTICORE WITH COPPER CONDUCTOR
0.6/1 kV XLPE INSULATED HALOJEN FREE FLAME RETARDANT MULTICORE WITH COPPER CONDUCTOR
Code | N2XH |
Standarts | TS HD 604 S1 ,VDE 0276 |
Construction | Copper Conductor, XLPE Insulation, HFFR filler , HFFR Outer Sheath |
Application | Used in energy networks in hotels,schools, high constructions,hospitals, power plants,data processing centers, business centers where there is a risk of fire. |
Technical Datas | Max. operating temperature 90°C
Max. short circuit temperature 250°C Min. Bending radius 12*D D: Cable overall Dia. (mm) |
- Product Description
Dimensions and Weights | Electrical Information | ||||
cross-section |
Diameter |
|
Delivery reel size for 1000m cable |
Conductor DC (maks.) resistance at 20 °C (maks.) |
Current carrying capacity in |
|
|||||
mm² | mm | kg/km | cm | ohm/km | |
2x1.5 re
|
9,5
|
120
|
80
|
12,1
|
26
|
2x2.5 re
|
10,0
|
150
|
90
|
7,41
|
36
|
2x4 re
|
11,0
|
200
|
90
|
4,61
|
49
|
2x6 re
|
12,0
|
250
|
100
|
3,08
|
63
|
2x10 rm
|
15,0
|
420
|
100
|
1,83
|
86
|
2x16 rm
|
17,0
|
550
|
120
|
1,15
|
115
|
2x25 rm
|
20,0
|
820
|
130
|
0,727
|
149
|
2x35 rm
|
22,5
|
1050
|
130
|
0,524
|
185
|
2x50 rm
|
25,5
|
1400
|
150
|
0,387
|
225
|
2x70 rm
|
29,0
|
1950
|
160
|
0,268
|
245 |
2x95 rm
|
33,0
|
2550
|
180
|
0,193
|
297 |
2x120 rm
|
36,0
|
3250
|
220
|
0,153
|
346 |
2x150 rm
|
40,5
|
3950
|
220
|
0,124
|
398 |
2x185 rm
|
45,0
|
5000
|
240
|
0,099
|
455 |
2x240 rm
|
49,0
|
6200
|
220*
|
0,0754
|
535 |