0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES
0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES

0.6/1 kV XLPE INSULATED, PVC SHEATHED, MULTICORE WITH COPPER CONDUCTOR POWER CABLES

• YXV
• N2XY

Öznur icon
Code YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts TS IEC 60502-1, VDE 0276
Construction Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights
Electrical Information
 
Nominal
cross-section
 
Overall
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
2x1.5 re
10,5
150
80
12,1
37
26
2x2.5 re
11,0
180
90
7,41
49
36
2x4 re
12,0
230
90
4,61
64
49
2x6 re
13,0
285
100
3,08
79
63
2x10 rm
16,0
450
110
1,83
106
86
2x16 rm
18,0
600
120
1,15
137
115
2x25 rm
21,0
860
130
0,727
176
149
2x35 rm
23,0
1100
130
0,524
213
185
2x50 rm
26,0
1420
150
0,387
252
225
2x70 rm
30,0
2000
180
0,268
-
-
2x95 rm
33,0
2600
200
0,193
-
-
2x120 rm
37,0
3300
220
0,153
-
-
2x150 rm
41,0
4000
230
0,124
-
-
2x185 rm
46,0
5000
240
0,0991
-
-
2x240 rm
50,0
6350
210*
0,0754
-
-
re:Single-wire conductor, rm:Stranded conductor, * For 500 m lenght cables