0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES
0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES

0.6/1 kV XLPE INSULATED, PVC SHEATHED, MULTICORE WITH COPPER CONDUCTOR POWER CABLES

• YXV
• N2XY

Öznur icon
Code YXV-U, YXV-R (TSE), N2XY (VDE)
Standarts TS IEC 60502-1, VDE 0276
Construction Copper Conductor, XLPE Insulation, PVC Filler Sheath, PVC Outer Sheath
Application These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights Electrical Information
 
Nominal 
cross-section
 
Overall 
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
3x1.5 re
11,0
165
90
12,1
30
23
3x2.5 re
12,0
210
90
7,41
40
32
3x4 re
12,5
265
90
4,61
52
42
3x6 re
14,0
345
100
3,08
64
53
3x10 rm
17,0
525
110
1,83
86
73
3x16 rm
19,0
730
120
1,15
111
98
3x25 rm
22,0
1080
130
0,727
143
126
3x35 rm
24,5
1400
140
0,524
173
156
3x50 rm
27,0
1840
160
0,387
205
190
3x70 rm
32,0
2580
180
0,268
252
245
3x95 rm
35,0
3430
200
0,193
303
297
3x120 rm
39,0
4330
220
0,153
346
346
3x150 rm
44,0
5220
230
0,124
390
398
3x185 rm
48,5
6600
210*
0,0991
441
455
3x240 rm
54,0
8350
230*
0,0754
511
535
3x300 rm
60,0
10650
250*
0,0601
580
630
3x400 rm
67,0
13600
220**
0,0470
663
740
re:Single-wire conductor, rm:Stranded conducto, * For 500 m lenght cables, ** For 250 m lenght cables