0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES
0.6/1 kV XLPE INSULATED PVC SHEATHED MULTICORE WITH COPPER CONDUCTOR POWER CABLES

0.6/1 kV XLPE INSULATED, PVC SHEATHED, MULTICORE WITH COPPER CONDUCTOR POWER CABLES

• YXV
• N2XY

Öznur icon
Code YXV-R (TSE), N2XY (VDE)
Standarts TS IEC 60502-1, VDE 0276
Construction Copper Conductor, XLPE Insulation ,PVC Filler Sheath, PVC Outer Sheath
Application These cables have a low dielectric loss, used in energy networks with sudden load change,installed mainly in residential or industrial areas. May be laid outdoors, underground or in ducts.
Technical Datas Max. operating temperature 90 °C
Max. short circuit temperature 250 °C
Min. Bending radius 12*D D: Cable overall Dia. (mm)
  • Product Description
Dimensions and Weights Electrical Information
 
Nominal
cross-section
 
Overall
Diameter
 
Net Weight
Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
 
Ground(A)
 
Air(A)
mm²
mm
kg/km
cm
ohm/km
3x16/10 rm
19,5
825
130
1,15
111
98
3x25/16 rm
23,0
1200
140
0,727
143
126
3x35/16 rm
25,0
1540
150
0,524
173
156
3x50/25 rm
29,0
2050
160
0,387
205
190
3x70/35 rm
33,0
2900
200
0,268
252
245
3x95/50 rm
37,0
3850
220
0,193
303
297
3x120/70 rm
41,5
4950
230
0,153
346
346
3x150/70 rm
45,0
5800
240
0,124
390
398
3x185/95 rm
51,0
7450
210*
0,0991
441
455
3x240/120 rm
56,0
9350
230*
0,0754
511
535
3x300/150 rm
63,0
12050
280*
0,0601
580
630
3x400/185 rm
70,0
15400
220**
0,0470
663
740
rm:Stranded conductor, * For 500 m lenght cables, ** For 250 m lenght cables