• YVV(TSE)
• NYY (VDE)
• Cu/PVC/PVC(BS)
0.6/1 kV PVC INSULATED SINGLE CORE CABLES WITH COPPER CONDUCTOR
0.6/1 kV PVC INSULATED SINGLE CORE CABLES WITH COPPER CONDUCTOR
Code | YVV-U, YVV-R (TSE), NYY (VDE), Cu/PVC/PVC (BS) |
Standarts | TS IEC 60502-1, VDE 0276 |
Construction | Copper conductor, PVC insulation, PVC outer sheath |
Application | Preferably for installation indoors, in cable ducts and in industrial plants or switching stations underground installation with additional protection where mechanical damage is unexpected. |
Technical Datas | Max. Operating temperature 70 °C
Max. Short circuit temperature <=300 mm² for 160 °C > 300 mm² for 140 °C Min. Bending radius 15*D D:Cable outer diameter (mm) |
- Product Description
Dimensions and Weights | Electrical Information | |||||||
cross-section |
Diameter |
Net Weight
|
Delivery reel size for 1000m cable
|
Conductor DC (max.) resistance at 20 °C (max.) |
Current carrying capacity in | |||
Ground(A)
|
Air(A)
|
|||||||
mm²
|
mm
|
kg/km | cm | ohm/km | ••• | ••• | ||
1x4 re
|
7,5
|
90
|
80
|
4,61
|
56
|
48
|
45
|
32
|
1x6 re
|
8,0
|
110
|
80
|
3,08
|
70
|
60
|
58
|
40
|
1x10 rm |
9,5
|
160
|
80
|
1,83
|
95
|
80
|
78
|
60
|
1x16 rm |
10,0
|
220
|
90
|
1,15
|
123
|
105
|
108
|
80
|
1x25 rm |
11,5
|
320
|
90
|
0,727
|
160
|
137
|
140
|
110
|
1x35 rm |
13,0
|
425
|
100
|
0,524
|
190
|
162
|
175
|
135
|
1x50 rm |
14,0
|
550
|
100
|
0,387
|
225
|
192
|
210
|
165
|
1x70 rm |
16,0
|
760
|
110
|
0,268
|
272
|
235
|
270
|
210
|
1x95 rm |
18,0
|
1020
|
120
|
0,193
|
320
|
284
|
330
|
260
|
1x120 rm |
19,5
|
1280
|
120
|
0,153
|
375
|
320
|
385
|
300
|
1x150 rm |
22,0
|
1525
|
130
|
0,124
|
420
|
360
|
448
|
350
|
1x185 rm |
24,0
|
1950
|
140
|
0,0991
|
475
|
410
|
510
|
400
|
1x240 rm |
26,5
|
2450
|
150
|
0,0754
|
550
|
475
|
600
|
480
|
x300 rm |
30,0
|
3175
|
160
|
0,0601
|
632
|
542
|
678
|
549
|
1x400 rm |
33,0
|
4050
|
180
|
0,0470
|
730
|
624
|
817
|
657
|
1x500 rm |
38,0
|
5150
|
210
|
0,0366
|
823
|
698
|
940
|
749
|